SolarAPP+ Eligibility Checklist
SolarAPP PV Eligibility 4/26/2021 |
System |
New Rooftop Residential PV Systems Only |
Installed by contractor with all licenses required by jurisdiction |
No building integrated solar systems |
Electrical |
Limited to 2017 NEC |
600V Max per DC System Size |
Single phase only |
No Aluminum Wires |
Must Use 600V rated PV wire (due to outer diameter > 0.24" (6.1mm)) |
Must use 90 deg C rated insulated wire |
Height of rooftop conduit > = 7/8" |
Max 2 DC strings in parallel |
Max 9 current carrying conductors in a raceway |
Inverter output circuit conductors must be THWN-2, or listed NM |
Terminals must be rated to 75 deg C, labeled for use with Cu wires, and accept minimum 8 AWG wire |
If using microinverter, 1 module per microinverter |
Permitted to install on up to or equal to 400A Service |
Permitted to install on up to or equal to 225A Service Disconnect |
Permitted to install on up to or equal to 225A busbars |
No existing PV on site |
May install only 1 module type |
May install only 1 racking system type |
May install up to 2 Inverters for String Inverters, up to 1 inverter type for Micro-inverters and AC modules Systems |
Conduit may not be Schedule 80 PVC |
Single Family Dwelling Only |
Modules and Inverters must be listed on CEC |
Rapid Shutdown cannot be satisfied using the method: No exposed wiring or conductive parts [690.12(B)(2)(3)] |
Flat Plate PV Modules Only |
No trenching allowed |
All power production inverter outputs have the same point of connection |
Structural |
2018 IBC |
PV system + hardware weight is less than or equal to 4psf |
Limited to 10” above the roof for pitched (>2/12) roof |
No metal roof or low-slope roof in areas with > 15psf snow load |
No wood shake or wood shingle roofing |
No carports or non-permanent structures |
No ground mounted systems |
Only one type of mounting hardware system per project |
Fire |
2018 IRC |